Dimensions W x L x H | (incl. interlinking block and connection system) 50 mm x 107 mm x 70 mm |
Width dimension | 50 mm |
Type code | CPX-P |
No. of inputs | 8 |
Diagnostics | Wire break per channel Limit value violation per channel Short circuit per channel Parameterization error |
Parameterization | Data format Input debouncing time per channel Input function per channel Replacement value in diagnostic case per channel Signal extension time per channel Gate time per channel Limit value monitoring per channel Short circuit monitoring per channel Parameter monitoring Counter configuration per channel Upper limit per channel Lower limit value per channel Wire break monitoring per channel |
Reverse polarity protection | for operating voltage |
Additional functions | Frequency measurement Counter function |
Control elements | DIL switch |
LED indicators | 1 group diagnostics 8 channel diagnostics 8 channel status |
Input debounce time | 3 ms (0 ms, 10 ms, 20 ms parameterizable) |
Fuse protection (short circuit) | Per channel |
Intrinsic current consumption at nominal operating voltage | Typ. 75 mA |
Nominal operating voltage DC | 24 V |
Power failure buffering | 20 ms |
Electrical isolation between channel and internal bus | yes |
Electrical isolation between channels | no |
Residual ripple | 0.4 Vss |
Switching level | as per EN 60947-5-6 |
Permissible voltage fluctuations | +/- 25 % |
Storage temperature | -20 °C ... 70 °C |
Relative air humidity | 95 % Non-condensing |
Degree of protection | Depends on manifold block |
Ambient temperature | -5 °C ... 50 °C |
Product weight | 100 g |
Input characteristics | as per EN 60947-5-6 |
Max. cable length | 200 m |
Type of mounting | On interlinking block CPX-M-GE... |
Note on materials | RoHS-compliant |
Housing material | PA-reinforced PC |