Dimensions W x L x H | (incl. interlinking block and connection system) 50 mm x 107 mm x 50 mm |
Type code | CPX |
No. of inputs | 4 |
Diagnostics | Wire break per channel Limit value violation per channel Parameterization error |
Parameterization | Limit value monitoring per channel Cold junction compensation Unit of measurement Measured value smoothing Sensor type per channel Wire break monitoring per channel |
LED indicators | 1 group diagnostics 4 channel diagnostics |
Internal cycle time | 250 ms |
Repetition accuracy | 0.05 % at 25 °C |
Fuse protection (short circuit) | Internal electronic fuse per channel |
DC operating voltage range | 18 V ... 30 V |
Intrinsic current consumption at nominal operating voltage | 30 mA |
Operating error limit related to the ambient temperature range | ±0.6 % |
Basic error limit at 25°C | ±0.4 % |
Max. line resistance | 10 ohm/conductor |
Nominal operating voltage DC | 24 V |
Electrical isolation between channel and internal bus | yes |
Electrical isolation between channels | no |
Corrosion resistance class (CRC) | 1 - Low corrosion stress (when installed) |
Storage temperature | -20 °C ... 70 °C |
Ambient temperature | -5 °C ... 50 °C |
Product weight | 46 g |
Data format | 15 bit + sign Binary representation in tenths of a degree |
Max. cable length | 50 m Shielded |
Sensor type | Type B Type E Type J Type K Type N Type R Type S Type T |
Housing material | PA-reinforced PC |