Your cart
There are no more items in your cart
Dimensions W x L x H | (incl. interlinking block) 50 mm x 107 mm x 50 mm |
Type code | CPX |
Fieldbus interface | 2x socket, M12x1, 4-pin, D-coded |
Device-specific diagnostics | Channel-oriented and module-oriented diagnostics Undervoltage of modules Diagnostic memory |
Configuration support | ESI file |
Parameterization | Diagnostic behavior Fail-safe response forcing of channels Signal setup System parameter |
Additional functions | Acyclic data access via fieldbus Diagnostic object Emergency message Compatibility mode with FB38 Modular Device Profile (MDP) System status can be indicated via process data Variable PDO mapping Additional diagnostic interface for operator units |
Control elements | DIL switch |
Baud rate | 100 Mbit/s |
DC operating voltage range | 18 V ... 30 V |
Intrinsic current consumption at nominal operating voltage | Typ. 100 mA |
Nominal operating voltage DC | 24 V |
Corrosion resistance class (CRC) | 1 - Low corrosion stress |
Storage temperature | -20 °C ... 70 °C |
Degree of protection | IP65 IP67 |
Ambient temperature | -5 °C ... 50 °C |
Product weight | 125 g |
Max. address capacity outputs | 128 byte |
Max. address capacity inputs | 128 byte |
Protocol | EtherCAT |
LED display (bus-specific) | Error: communication error LA X1: network active, port 1 LA X2: network active, port 2 Run: communication status |
LED display (product-specific) | M: Modify, parameterization PL: load supply PS: electronics supply, sensor supply SF: system fault |
Note on materials | RoHS-compliant |
Housing material | PA-reinforced |